Quantum Secular Labs / Blog / Advisories

CVE-2016-7112: Siemens En100 Ethernet Module Firmware: Improper Authentication

CVE-2016-7112 is rated critical with a CVSS v3.0 base score of 9.8 and NVD lists Siemens En100 Ethernet Module Firmware as the affected product. Per its scoring, it can be exploited over the network, without authentication, without any user interaction. The scored impact on confidentiality, integrity and availability is the highest available.

Vulnerability description

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations.

Severity breakdown

CVSS v3.0 9.8: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

  • Attack vector: Network. Exploitable remotely over the network, with no need for local or physical access.
  • Attack complexity: Low. No special conditions; the attack can be repeated reliably.
  • Privileges required: None. No account or prior access is needed.
  • User interaction: None. No action from any user is needed.
  • Scope: Unchanged. Impact stays within the vulnerable component.
  • Confidentiality impact: High. Total loss of confidentiality; sensitive data can be fully disclosed.
  • Integrity impact: High. Total loss of integrity; data or system state can be fully modified.
  • Availability impact: High. Total loss of availability; the component can be shut down.

Underlying weakness

CWE-287: Improper Authentication

When an actor claims to have a given identity, the product does not prove or insufficiently proves that the claim is correct.

Affected products

  • Siemens En100 Ethernet Module Firmware: up to and including 4.28

References